FR · DE · EN
Quote request (0)
WS-SMART-HG

Heating plant control

Turnkey boiler-room control for refurbishment: it replaces an end-of-life controller without touching the existing hydraulics. Up to six heating circuits, two DHW boilers, district heating, generator cascade. Wiring through chained WS-Smart-IO modules; web supervision, BACnet or Modbus to the existing BMS.

  • 6 heating circuits
  • 2 DHW cylinders
  • District heating
  • BACnet / Modbus

Pre-production series: CE conformity assessment in progress. Availability and lead time confirmed in the quotation. For sizing, call +41 27 326 60 00.

Example · district heating substation

Connected to district heating, the substation delivers heat to the building's heating circuits, and they are what sets the return temperature. WS-SMART-HG measures the primary return and the return of each circuit, reads the heat meter over M-Bus and the actual position of the primary valve, and makes these points available to the network operator's supervision system over BACnet or Modbus.

Schematic of a district heating substation controlled by WS-SMART-HG, 12 numbered points
  1. 1Primary supply and return pressure
  2. 2Heat meter (M-Bus)
  3. 3Primary valve, position feedback
  4. 4Primary supply temperature
  5. 5Primary return temperature
  6. 6Secondary temperatures
  7. 7Secondary safety thermostat
  8. 8Outdoor temperature
  9. 9Heating circuit temperatures
  10. 103-way valve, position feedback
  11. 11Circulator, current measured
  12. 12DHW: cylinder and charging pump
  13. In red: value set by the network operator
Reference configuration 1ECH-4GR-1ECS, from the published wiring diagram (Downloads): one heat exchanger, four heating circuits, one DHW circuit. Up to two heat exchangers, six heating circuits and two DHW cylinders. Open the schematic full size

What the controller changes

Manual valve overrides detected

Each actuator reports its real position: a valve turned by hand, jammed or disengaged flags itself.

Pumps watched through their current

The circulator output measures current from 0 to 10 A, detection from 0.2 A: a pump that does not start or runs dry is seen at once.

Open to a third-party controller

WS-Smart-IO modules are standard Modbus RTU slaves, up to fifteen per bus: a controller with a Modbus RTU master drives them directly, without the WS-HG controller.

Wiring counted by the metre

Modules are chained from box to box, bus and 230 V included: no more harness to bring back group by group to the cabinet.

The film

A boiler-room controller can be replaced without touching the hydraulics. The film shows the modules chained circuit by circuit, the detection of manually forced valves and stopped pumps, then the Modbus opening. 56 seconds, no sound needed.

WS-SMART-HG in 56 seconds Open the film full screen Vertical 9:16 · 56 seconds

The hardware

Specifications

Technical specifications · WS-SMART-HG
Heating circuitsUp to 6, independent
Domestic hot water2 cylinders with priority, built-in anti-legionella cycle
District heating1 or 2 heat exchangers, or conventional heating
Heating curves2 or 5 points
Heat sourcesCascade of mixed heat sources: heat pump, gas, biomass, electric backup
Summer / winter changeoverAutomatic
OptimisationFlow temperatures adjusted to actual demand
Power managementPower limitation and load peak shaving
ValvesPosition feedback: detection of manual override or local operation
PumpsControl with current sensing for monitoring and maintenance
Supervisory systemFully web-based interface, local access or secure remote access
LoggingIntegrated data logging and energy monitoring
Safety functionsFrost, overheating, sensor fault, pump fault
AlarmsDetailed alarms, configurable notifications
CyclingFewer short cycles: longer heat source life
CommunicationBACnet and Modbus, integration into an existing BMS
ExpansionWS-Smart-IO modules, each: 2 RTD inputs · 2 digital inputs · 2 × 0–10 V actuator outputs · 1 Modbus RTU · 1 × 230 V output to enable the circulating pump
ArchitectureModular and expandable, up to several substations
ManufacturerWellset
Restocking lead timeConfirmed in the quotation

Wiring the WS-SMART-IO modules

The bus arrives on J1 and leaves on J2 (24 VAC, Modbus RTU, A to A, B to B). The 230 V arrives on J10 and leaves on J11; the pump connects to J12 and its enable contact to J13.

PT1000 sensors on J14, safety thermostat on J5, 24 VAC actuator on J3. One address per module, TERM on ON at the last module only. Switch off at the cabinet before opening a module: the 230 V arrives through the chain.

52 seconds, no sound.

Downloads

Compatible parts